Output Function Summary Table - Omron MX2 User Manual

200 v class three-phase input 0.1 to 15 kw 200 v class single-phase input 0.1 to 2.2 kw 400 v class three-phase input 0.4 to 15 kw
Hide thumbs Also See for MX2:
Table of Contents

Advertisement

"C" Group: Intelligent Terminal Functions
Option
Terminal
Code
Symbol
00
RUN
01
FA1
02
FA2
03
OL
04
OD
05
AL
06
FA3
07
OTQ
09
UV
10
TRQ
11
RNT
12
ONT
13
THM
19
BRK
20
BER
Output Function Summary Table - This table shows all functions for the log-
ical outputs (terminals [11], [12] and [AL]) at a glance. Detailed descriptions of
these functions, related parameters and settings, and example wiring dia-
grams are in 4-6 Using Intelligent Output Terminals on page 198.

Output Function Summary Table

Function Name
Run Signal
ON
OFF
Frequency Arrival Type
ON
1-Constant Speed
OFF
Frequency Arrival Type
ON
2-Over frequency
OFF
Overload Advance
ON
Notice Signal 1
OFF
Output Deviation for
ON
PID Control
OFF
Alarm Signal
ON
OFF
Frequency Arrival Type
ON
3-Set frequency
OFF
Over/under Torque Sig-
ON
nal
OFF
Undervoltage
ON
OFF
Torque Limited Signal
ON
OFF
Run Time Expired
ON
OFF
Power ON time Expired ON
OFF
Thermal Warning
ON
OFF
Brake Release Signal
ON
OFF
Brake Error Signal
ON
OFF
Description
When the inverter is in Run Mode
When the inverter is in Stop Mode
When output to motor is at the set frequency
When output to motor is OFF, or in any acceleration
or deceleration ramp
When output to motor is at or above the set freq.,
even if in accel (C042) or decel (C043) ramps
When output to motor is OFF, or at a level below the
set frequency
When output current is more than the set threshold
(C041) for the overload signal
When output current is less than the set threshold for
the deviation signal
When PID error is more than the set threshold for
the deviation signal
When PID error is less than the set threshold for the
deviation signal
When an alarm signal has occurred and has not
been cleared
When no alarm has occurred since the last cleaning
of alarm(s)
When output to motor is at the set frequency, during
accel (C042) and decel (C043).
When output to motor is OFF, or is not at a level of
the set frequency
Estimated motor torque exceeds the specified level
Estimated motor torque is lower than the specified
level
Inverter is in Undervoltage
Inverter is not in Undervoltage
Torque limit function is executing
Torque limit function is not executing
Total running time of the inverter exceeds the speci-
fied value
Total running time of the inverter does not exceed
the specified value
Total power ON time of the inverter exceeds the
specified value
Total power ON time of the inverter does not exceed
the specified value
Accumulated thermal count exceeds the C061 set
value
Accumulated thermal count does not exceed the
C061 set value
Output for brake release
No action for brake
Brake error has occurred
Brake performance is normal
Section 3-7