Test The Ac Outlet - Avaya G700 Installation And Upgrades

Media gateway controlled by media server
Hide thumbs Also See for G700:
Table of Contents

Advertisement

2 Installing Hardware for the G700 Media Gateway and S8300 Media Server: Installation and Cabling

Test the AC Outlet

!
WARNING:
The following recommended test equipment, tests and diagrams are intended only for
North American installations at 110 to 125 Volts AC. For installations in other
regions, have a licensed electrician verify the ground and voltages.
!
WARNING:
If the AC outlet tests indicate that the power requirements are not met, your customer
must contact a licensed electrician. DO NOT install the system until all requirements
are met.
Fault Conditions
If the AC outlet tests that follow reveal any of the following conditions, they must be corrected
BEFORE the system is to be installed.
• Open ground
• Hot and neutral reversed
• Open hot
• Open neutral
• Hot and ground reversed
!
WARNING:
Hazardous voltages are present during this test. Follow all instructions carefully
when working the AC power line voltages.
Verify Ground Using an Ideal 61-035 Circuit Tester (or equivalent)
Plug the circuit tester into the outlet that you want to test.
1.
If the circuit is properly grounded, the yellow and white lights on the tester illuminate
Unplug the tester.
2.
!
WARNING:
If the tester indicates any type of ground fault, your customer must contact a licensed
electrician. DO NOT install the system.
Verify Voltages Using a Volt-Ohm Millimeter (VOM) (U.S. and countries using 110 to 125 V AC
power)
!
WARNING:
Hazardous voltages are present during this test. Follow all instructions carefully
when working with AC power line voltages.
Ensure that the VOM is set to read Volts AC
1.
2.
Set the VOM to the lowest scale on which you can read 130 V AC.
Installation and Upgrades for G700 with S8300 or S8700
555-234-100 — Issue 3 — May 2003
85

Advertisement

Table of Contents
loading

This manual is also suitable for:

S8300S8700

Table of Contents