Clock Instructions

3-28-5 CLOCK ADJUSTMENT: DATE(735)

Purpose
Ladder Symbol
Variations
Applicable Program Areas
Operands
Changes the internal clock setting to the setting in the specified source words.
Note The internal clock setting can also be changed from a Peripheral Device or
the CLOCK WRITE FINS command (0702).
DATE(735)
S
Variations
Executed Each Cycle for ON Condition
Executed Once for Upward Differentiation
Executed Once for Downward Differentiation Not supported.
Immediate Refreshing Specification
Block program areas
OK
S through S+3: New Clock Setting
Set the new clock setting in S through S+3 as shown in the following diagram.
S through S+3 must be in the same data area.
15
S
15
S+1
15
S+2
15
S+3
S: First source word
Step program areas
Subroutines
OK
OK
8
7
0
Seconds: 00 to 59 (BCD)
Minutes: 00 to 59 (BCD)
8
7
0
Hour: 00 to 23 (BCD)
Day: 01 to 31 (BCD)
8
7
0
Month: 01 to 12 (BCD)
Year: 00 to 99 (BCD)
8
7
0
Day of the week: 00 = Sunday
Always set to 00.
Section 3-28
DATE(735)
@DATE(735)
Not supported.
Interrupt tasks
OK
01 = Monday
02 = Tuesday
03 = Wednesday
04 = Thursday
05 = Friday
06 = Saturday