Omron SYSMAC CJ - REFERENCE MANUAL 01-2008 Reference Manual page 1314

Sysmac cs/cj/one nsj series programmable controllers
Table of Contents

Advertisement

Model Conversion Instructions (Unit Ver. 3.0 or Later)
Description
Flags
Area
EM Area with bank
Indirect DM/EM
addresses in binary
Indirect DM/EM
addresses in BCD
Constants
Data Registers
Index Registers
Indirect addressing
using Index Registers
MOVBC(568) copies the specified bit (n) from S to the specified bit (m) in D.
The other bits in the destination word are left unchanged.
Note The same word can be specified for both S and D to copy a bit within a word.
Name
Error Flag
ER
Note In C-series PLCs, the MOVE BIT (MOVB) instruction will cause the Error Flag
to go ON if the content of an indirectly addressed DM word (*DM) is not BCD,
or the DM area boundary is exceeded. MOVBC(568) will not cause the Error
Flag to go ON in these cases.
S
En_00000 to En_32767
(n = 0 to C)
@ D00000 to @ D32767
@ E00000 to @ E32767
@ En_00000 to @ En_32767
(n = 0 to C)
*D00000 to *D32767
*E00000 to *E32767
*En_00000 to *En_32767
(n = 0 to C)
#0000 to #FFFF
(binary)
DR0 to DR15
---
,IR0 to ,IR15
–2048 to +2047, IR0 to –2048 to +2047, IR15
DR0 to DR15, IR0 to IR15
,IR0+(++) to ,IR15+(++)
,–(– –) IR0 to, –(– –) IR15
Label
ON if the rightmost and leftmost two digits of C are not
BCD or outside of the specified range of 00 to 15.
OFF in all other cases.
Section 3-35
C
Specified values
---
only
Operation
D
1275