4-5-25 Limit signal of homing, Trigger signal of zero-return

These functions are used for homing performance.
One of three types of homing operations can be selected by homing mode
P068
selection (
). When a homing operation ends, the current position counter
is cleared (to 0). Use homing direction selection (
of homing operation. If homing operation is not performed, position control is
performed based on the assumption that the motor position detected at
power-on is the origin.
<1> Low speed homing (P068=00)
ORG
ON
ORL
(2)
Output
freq.
(1)
<2> High speed homing (P068=01)
ORG
ON
ORL
(2)
Output
freq.
(1)
Origin
1. The inverter accelerates the
motor for the specified ramp time
to the low speed homing.
2. It runs the motor at the low
ON
speed homing.
Low speed homing
3. It performs positioning when the
(P070)
(3)
ORL signal is given.
Origin
Position
1. The inverter accelerates the mo-
tor for the specified ramp time to
the high speed homing.
(5)
2. It runs the motor at the high
ON
speed homing.
High speed homing
3. It starts deceleration when the
(P071)
(3)
ORL signal is turned on.
4. It runs the motor in the reverse
Position
(4)
(5)
direction at the low speed hom-
Low speed homing
(P070)
ing.
5. It performs positioning when the
ORL signal is turned off.
Section 4-5
P069
) to select the direction
195