Zero Hz Speed Detection Signal - Omron MX2 User Manual

200 v class three-phase input 0.1 to 15 kw 200 v class single-phase input 0.1 to 2.2 kw 400 v class three-phase input 0.4 to 15 kw
Hide thumbs Also See for MX2:
Table of Contents

Advertisement

Using Intelligent Output Terminals

4-6-16 Zero Hz Speed Detection Signal

The inverter outputs the 0Hz speed detection signal when the inverter output
frequency falls below the threshold level (
To use this function, assign "21 (ZS)" to one of the intelligent output terminals.
Option
Terminal
Code
Symbol
21
ZS
Zero Hz
speed
detection
signal
Valid for inputs:
11, 12, AL0 - AL2
C063
Required settings:
Notes:
• The example circuit for terminal [11] drives a relay coil. Note the use of a diode to
prevent the negative-going turn-off spike generated by the coil from damaging the
inverter's output transistor.
C063
).
Function
State
Name
Output frequency is less than C063
ON
OFF
Output frequency is not less than
C063
Section 4-6
Description
211