Omron MX2 User Manual page 150

200 v class three-phase input 0.1 to 15 kw 200 v class single-phase input 0.1 to 2.2 kw 400 v class three-phase input 0.4 to 15 kw
Hide thumbs Also See for MX2:
Table of Contents

Advertisement

"B" Group: Fine Tuning Functions
Func.
Code
b171
Inverter mode selection
Function
Rating
HD
Max. freq. (A004)
1000Hz
Start freq. (b082)
0.10 to 100.0 (Hz)
Carrier freq. (b083)
2.0 to 10.0 (kHz)
00: Const. torque
V/f characteristic curve
(A044)
01: Reduced torque
02: Free V/f
128
The inverter mode cannot be changed just setting b171. After setting b171, be
sure to execute initialization to activate new mode.
Actual inverter mode can be monitored with d060.
Once high frequency mode is set, initialization can be done just by setting
b084, b085, b094 and setting b180, it is not needed to set b171 .
"B" Function
Name
Main differences between high frequency and std. mode are as follows.
High frequency
mode
HD
400Hz
0.10 to 9.99 (Hz)
2.0 to 15.0 (kHz)
00: Const. torque
01: Reduced torque
02: Free V/f
03: SLV
HD mode
HD mode
b049: 00
d060: 1-C
b171 = 02
+ init.
High freq. mode
d060: H-1
High freq. ( 1000 Hz)
Description
Three option codes:
00
No function
01
Std. IM (Induction Motor)
02
High frequency IM
03
PM (Permanent Magnet Motor)
Standard mode
ND
400Hz
0.10 to 9.99 (Hz)
2.0 to 10.0 (kHz)
00: Const. torque
01: Reduced torque
02: Free V/f
Normal mode ( 400 Hz)
b049 = 01
b049 = 00
b171 = 01
+ init.
b171 = 03
+ init.
b171 = 02
+ init.
Section 3-6
Run
Defaults
Mode
EU
Units
Edit
00
Permanent Magnet
HD
400Hz
0.10 to 9.99 (Hz)
2.0 to 15.0 (kHz)
Not available
ND mode
ND mode
b049: 01
d060: 1-v
b171 = 03
+ init.
Permanent magnet
mode
d060: P
Permanent magnet mode