"A" Group: Standard Functions
Code
Run Command Source
03
ModBus network input - The network has a dedicated
coil for Run/Stop command and a coil for FW/RV
04
Option - Select when an option card is connected and
use the frequency source from the option
A001
A002
/
Override Sources - The inverter allows some sources to override
the setting for output frequency and Run command in
vides flexibility for applications that occasionally need to use a different
source, leaving the standard settings in
The inverter has other control sources that can temporarily override the
A001
parameter
setting, forcing a different output frequency source. The fol-
lowing table lists all frequency source setting methods and their relative prior-
ity ("1" is the highest priority).
Priority
A001 Frequency Source Setting Method
1
[CF1] to [CF4] Multi-speed terminals
2
[OPE] Operator Control intelligent input
3
[F-TM] intelligent input
4
[AT] terminal
5
A001 Frequency source setting
The inverter also has other control sources that can temporarily override the
A002
parameter
setting, forcing a different Run command source. The follow-
ing table lists all Run command setting methods and their relative priority ("1"
is the highest priority).
Priority
A002 Run Command Setting Method
1
[OPE] Operator Control intelligent input
2
[F-TM] intelligent input
3
A002 Run command source setting
The figure below shows the correlation diagram of all frequency source setting
methods and their relative priority.
Section 3-5
Refer to page(s)...
283
(manual of each
option)
A001
A002
and
A001
A002
/
.
Refer to page...
74
188
191
223
68
Refer to page...
188
191
68
. This pro-
69