Determining Wire And Fuse Sizes - Omron MX2 User Manual

200 v class three-phase input 0.1 to 15 kw 200 v class single-phase input 0.1 to 2.2 kw 400 v class three-phase input 0.4 to 15 kw
Hide thumbs Also See for MX2:
Table of Contents

Advertisement

Step-by-Step Basic Installation
2-3-6

Determining Wire and Fuse Sizes

Motor Output
kW
HP
VT
CT
VT
CT
0.2
0.1
¼
1/8
0.4
0.2
½
¼
0.55 0.4
¾
½
1.1
0.75 1.5
1
2.2
1.5
3
2
3.0
2.2
4
3
0.2
0.1
¼
1/8
0.4
0.2
½
¼
0.75 0.4
1
½
1.1
0.75 1.5
1
2.2
1.5
3
2
3.0
2.2
4
3
5.5
3.7
7.5
5
7.5
5.5
10
7.5
11
7.5
15
10
15
11
20
15
18.5 15
25
20
0.75 0.4
1
½
1.5
0.75 2
1
2.2
1.5
3
2
3.0
2.2
4
3
4.0
3.0
5
4
5.5
4.0
7.5
5
7.5
5.5
10
7.5
11
7.5
15
10
15
11
20
15
18.5 15
25
20
Note 1
Note 2
Note 3
Note 4
The maximum motor currents in your application determines the recom-
mended wore size. The following table gives the wire size in AWG. The
"Power Lines" column applies to the inverter input power, output wires to the
motor, the earth ground connection, and any other components shown in the
"Basic System Description" on page 26. The "Signal Lines" column applies to
any wire connecting to the two green connectors just inside the front cover
panel.
Inverter Model
MX2-AB001
AWG16 / 1.3 mm² (75°C only) 18 to 28 AWG /
MX2-AB002
MX2-AB004
MX2-AB007
AWG12 / 3.3 mm² (75°C only)
MX2-AB015
AWG10 / 5.3 mm²
MX2-AB022
MX2-A2001
AWG16 / 1.3 mm²
MX2-A2002
MX2-A2004
MX2-A2007
MX2-A2015
AWG14 / 2.1 mm² (75°C only)
MX2-A2022
AWG12 / 3.3 mm² (75°C only)
MX2-A2037
AWG10 / 5.3 mm² (75°C only)
MX2-A2055
AWG6 / 13 mm² (75°C only)
MX2-A2075
MX2-A2110
AWG4 / 21 mm² (75°C only)
MX2-A2150
AWG2 / 34 mm² (75°C only)
MX2-A4004
AWG16 / 1.3 mm²
MX2-A4007
MX2-A4015
MX2-A4022
AWG14 / 2.1 mm²
MX2-A4030
MX2-A4040
AWG12 / 3.3 mm² (75°C only)
MX2-A4055
AWG10/ 5.3 mm² (75°C only)
MX2-A4075
MX2-A4110
AWG6 / 13 mm² (75°C only)
MX2-A4150
AWG6 / 13 mm² (75°C only)
Field wiring must be made by a UL-Listed and CSA-certified closed-loop ter-
minal connector sized for the wire gauge involved. Connector must be fixed by
using the crimping tool specified by the connector manufacturer.
Be sure to consider the capacity of the circuit breaker to be used.
Be sure to use a larger wire gauge if power line length exceeds 66 ft. (20 m).
Use 18 AWG / 0.75 mm² wire for the alarm signal wire ([AL0], [AL1], [AL2] ter-
minals).
Wiring
Power Lines
Signal Lines
0.14 to
0.75 mm²
shielded wire
*4
Section 2-3
Applicable equipment
Fuse
(UL-rated, class J, 600 V)
10 A
15 A
30 A
10 A
15 A
20 A
30 A
40 A
80 A
80 A
10 A
15 A
20 A
40 A
40 A
37

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents