Output Logic And Timing; Logic Output Function - Omron MX2 User Manual

200 v class three-phase input 0.1 to 15 kw 200 v class single-phase input 0.1 to 2.2 kw 400 v class three-phase input 0.4 to 15 kw
Hide thumbs Also See for MX2:
Table of Contents

Advertisement

"C" Group: Intelligent Terminal Functions

3-7-10 Output Logic and Timing

Func.
Code
C142
C143
C144
C145
C146
C147
146
Logic Output Function - The inverter has a built-in logic output feature.
Select any two operands out of all intelligent output options and their operator
out of AND, OR, or XOR (exclusive OR). The terminal symbol for the new out-
put is [LOG]. Use C021, C022 or C026 to route the logical result to terminal
[11], [12] or the relay terminals. LOG1-LOG3, no, OPO cannot be the oper-
and.
Intelligent outputs
used as internal
C142/C145/C148
inputs:
RUN, FA1, FA2,
OL, OD, AL, Dc,
...EDM
C143/C146/C149
RUN, FA1, FA2,
OL, OD, AL, Dc,
...EDM
The following table shows all four possible input combinations with each of the
three available logic operations.
Operand
A
0
0
1
1
"
Name
Logic output 1 operand A
Logic output 1 operand B
Logic output 1 operator
Logic output 2 operand A
Logic output 2 operand B
Logic output 2 operator
C144/C147/C150
Operand A
AND, OR, XOR
Operand B
B
AND
0
0
1
0
0
0
1
1
C" Function
Description
All the programmable functions
available for logic (discrete) out-
puts except LOG1 to LOG3, OPO,
no
Applies a logic function to calcu-
late [LOG] output state,
Three options:
00... [LOG] = A AND B
01... [LOG] = A OR B
02... [LOG] = A XOR B
All the programmable functions
available for logic (discrete) out-
puts except LOG1 to LOG3, OPO,
no
Applies a logic function to calcu-
late [LOG] output state,
Three options:
00... [LOG] = A AND B
01... [LOG] = A OR B
02... [LOG] = A XOR B
Section 3-7
Operator
Operator
OR
0
0
1
1
1
1
1
0
Run
Mode
Edit
00
00
00
00
00
00
C021
11
C022
12
C026
AL1
AL0
AL2
XOR
Defaults
EU
Units

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents