"A" Group: Standard Functions

3-5-12 Second Acceleration and Deceleration Functions

A094
=
Output
frequency
Accel 1
0
1
2CH
input
0
Func.
Code
A092
A292
A093
A293
A094
A294
A095
A295
A096
A296
*1
Up to 1000Hz for High frequency mode (d060 set to "2")
*2
Up to 1000Hz for High frequency mode (d060 set to "2")
The MX2 inverter features two-stage acceleration and deceleration ramps.
This gives flexibility in the profile shape. You can specify the frequency transi-
tion point, the point at which the standard acceleration (
F003
(
) changes to the second acceleration (
you can use intelligent input [2CH] to trigger this transition. These profile
options are also available for the second motor settings. Select a transition
a094
method via
acceleration/deceleration settings with settings for the second motor!
Transition via 2CH input
00
Accel 2
=
00
t
"A" Function
Name
Acceleration time (2)
Acceleration time (2),
nd
2
motor
Deceleration time (2)
Deceleration time (2),
nd
2
motor
Select method to switch to
Acc2/Dec2 profile
Select method to switch to
Acc2/Dec2 profile, 2nd motor
Acc1 to Acc2 frequency transi-
tion point
Acc1 to Acc2 frequency transi-
tion point, 2nd motor
Dec1 to Dec2 frequency transi-
tion point
Dec1 to Dec2 frequency transi-
tion point, 2nd motor
A095
A096
Note For
and
Dec1 time (less than 1.0 second), the inverter may not be able to change
rates to Acc2 or Dec2 before reaching the target frequency. In that case, the
inverter decreases the rate of Acc1 or Dec1 in order to achieve the second
ramp to the target frequency.
as depicted below. Be careful not to confuse the second
A094
=
Transition via freq. level
01
Output
frequency
Accel 2
A095
Accel 1
Description
nd
2
segment of acceleration,
range is:
0.01 to 3600 sec.
nd
2
segment of deceleration,
range is:
0.01 to 3600 sec.
Three options for switching from
1st to 2nd accel/decel:
00... 2CH input from terminal
01... Transition frequency
02... Forward and reverse
Output frequency at which Accel1
switches to Accel2, range is 0.0 to
*1
400.0 Hz
Output frequency at which Decel1
switches to Decel2, range is 0.0 to
*2
400.0 Hz
(and for 2nd motor settings), if you set a very rapid Acc1 or
Section 3-5
F002
) or deceleration
a092
a093
) or deceleration (
decel 2
Frequency
Transition
points
decel 1
Run
Defaults
Mode
EU
Edit
10.00
10.00
10.00
10.00
00
00
0.0
0.0
0.0
0.0
). Or
A096
t
Units
sec
sec
sec
sec
Hz
Hz
Hz
Hz
93