"A" Group: Standard Functions
3-5-9

PID Sleep Function

3-5-10 Automatic Voltage Regulation (AVR) Function

Func.
Code
A081
a281
A082
a282
a083
a084
The inverter shuts off the output when the PID output becomes less than the
A156
specified value (
quency command becomes less than the specified value in case of PID is set
disabled. And if the PID output or frequency command exceeds the specified
A156
value (
) for a specified period (
operation. This is the PID sleep function.
PID output
PID sleep function
triggering level
A156
Run command (internal)
Run
Run command (external)
• PID Sleep function is always enabled, even the PID function is disabled.
The automatic voltage regulation (AVR) feature keeps the inverter output
waveform at a relatively constant amplitude during power input fluctuations.
This can be useful if the installation is subject to input voltage fluctuations.
However, the inverter cannot boost its motor output to a voltage higher than
the power input voltage. If you enable this feature, be sure to select the proper
voltage class setting for your motor.
"A" Function
Name
AVR function select
nd
AVR function select, 2
motor
AVR voltage select
nd
AVR voltage select, 2
motor
AVR filter time constant
AVR deceleration gain
Note The motor behave as generator during deceleration and the energy is regen-
erated to the drive. As a result, the DC voltage in the inverter increases and
cause over-voltage trip when exceeding the OV level. When the voltage is set
high, deceleration time can be set shorter thanks to the energy consumption
due to the increase of losses in inverter. In order to set deceleration time
shorter without over-voltage trip, please try to set AVR off during deceleration
or to tune the AVR filter time constant and AVR deceleration gain.
) in case of PID is set enabled, or shuts off when the fre-
A157
), inverter automatically restarts the
A157
PID sleep function action delay time
Stop
Run
Description
Automatic (output) voltage regula-
tion, selects from three type of
AVR functions, three option
codes:
00... AVR enabled
01... AVR disabled
02... AVR enabled except during
deceleration
200V class inverter settings:
200/215/220/230/240
400V class inverter settings:
380/400/415/440/460/480
Define the time constant of the
AVR filter, range is 0 to 10 sec.
Gain adjustment of the braking
performance, range is 50 to 200%
Section 3-5
A157
Run
Run
Defaults
Mode
EU
Units
Edit
02
02
230/
V
460
230/
V
460
0.30
sec
100.
%
91