Other Analog Input-Related Topics; Pulse Train Input Operation - Omron MX2 User Manual

200 v class three-phase input 0.1 to 15 kw 200 v class single-phase input 0.1 to 2.2 kw 400 v class three-phase input 0.4 to 15 kw
Hide thumbs Also See for MX2:
Table of Contents

Advertisement

Analog Input Operation
4-7-1

Other Analog Input-related topics:

4-7-2

Pulse Train Input Operation

224
Current Input – The current input circuit
uses terminals [OI] and [L]. The current
comes from a sourcing type transmitter; a
sinking type will not work! This means the
current must flow into terminal [OI], and ter-
minal [L] is the return back to the transmitter.
The input impedance from [OI] to [L] is
100 Ohms. Attach the cable shield wire only
to terminal [L] on the inverter.
See I/O specs on
page 169
The following table shows the available analog input settings. Parameter
and the input terminal [AT] determine the External Frequency Command input
terminals that are available, and how they function. The analog inputs [O] and
[OI] use terminal [L] as the reference (signal return).
A005
[AT] Input
00
ON
OFF
02
ON
OFF
03
ON
OFF
• "Analog Input Settings"
• "Additional Analog Input Settings"
• "Analog Signal Calibration Settings"
• "Analog Input Current/Voltage Select"
• "ADD Frequency Enable"
• "Analog Input Disconnect Detect"
The MX2 inverter is capable of accepting pulse train input signals, that are
used for frequency command, process variable (feedback) for PID control,
and simple positioning. The dedicated terminal is called "EA" and "EB". Termi-
nal "EA" is a dedicated terminal, and the terminal "EB" is an intelligent termi-
nal, that has to be changed by a parameter setting.
Relay contact
AL2 AL1 AL0
Terminal Name
EA
Pulse train input A
EB
Pulse train input B
(Set C007 to 85 )
(Input terminal 7)
.
Analog Input Configuration
[O]
[OI]
[O]
Integrated POT on external panel
[OI]
Integrated POT on external panel
RS485
comm.
Logic input
SN
7
6
5
4
SP EO
EA
H
O
OI
RS485
Pulse
Pulse
Analog
comm.
Train
Train
input
output
input
Description
For frequency command,
32 kHz max.
Common is [L]
27 VDC max.
For frequency command,
2 kHz max.
Common is [PLC]
Section 4-7
AM H
O
OI
L
4 to 19.6 mA DC,
4 to 20 mA nominal
A005
3
2
1
L
PLC P24
Short bar
L
AM CM2
12 11
Analog
Logic
output
output
Ratings

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents