Frequency conversion coefficient setting: b086 – By setting b086, con-
verted output frequency is monitored in d007. (d007 = d001 x b086)
Frequency set in monitoring: b163 – If 01 is set in b163, frequency can be
changed by up/down key in monitor display d001 and d007.
Action selection in case of external operator disconnection: b165 –
When an external operator is disconnected, the inverter behaves according to
b165 setting.
"B" Function
Name
Initial display selection
Frequency scaling conversion
factor
Display ex.operator connected When an external operator is con-
st
1
parameter of Dual Monitor
nd
2
parameter of Dual Monitor
Frequency set in monitoring
Automatic return to the initial
display
Ex. operator com. loss action
Note If the power is off with displaying "000" after the set, b038 comes when power
is on again.
Description
000 Func. code that
key
pressed last displayed.(*)
001~030 d001~d030 displayed
201
F001 displayed
202
B display of LCD operator
Specify a constant to scale the
displayed frequency for D007 mon-
itor, range is 0.01 to 99.99
nected via RS-422 port, the built-
in display is locked and shows
only one "d" parameter configured
in:
d001 ~ d030
Set any two "d" parameters in
b160 and b161, then they can be
monitored in d050. The two
parameters are switched by up/
down keys.
Set range: d001 ~ d030
Two option codes:
00
Freq. set disabled
01
Freq. set enabled
10 min. after the last key opera-
tion, display returns to the initial
parameter set by b038. Two option
codes:
00
Disable
01
Enable
Five option codes:
00
Trip
01
Trip after deceleration to a
stop
02
Ignore
03
Coasting (FRS)
04
Decelerates to a stop
Section 3-6
Run
Defaults
Mode
EU
Units
Edit
001
1.00
001
001
002
00
00
02