Set The Motor Base Frequency And Avr Voltage Of The Motor - Omron MX2 User Manual

200 v class three-phase input 0.1 to 15 kw 200 v class single-phase input 0.1 to 2.2 kw 400 v class three-phase input 0.4 to 15 kw
Hide thumbs Also See for MX2:
Table of Contents

Advertisement

Using the Front Panel Keypad
!Caution If you operate a motor at a frequency higher than the inverter standard default
52
If the Potentiometer Enable LED is OFF, follow these steps below (the table
resumes action from the end of the previous table).
Action
(Starting point)
Press the
key
Press the
key
Press the
/
Press the
key to store
Note After completing the steps above, the Run Key Enable LED will be ON. This
does not mean the motor is trying to run; it means that the RUN key is now
enabled. DO NOT press the RUN key at this time – complete the parameter
setup first.
3. Set the Motor Base Frequency and AVR voltage of the motor – The
motor is designed to operate at a specific AC frequency. Most commercial
motors are designed for 50/60 Hz operation. First, check the motor specifica-
tions. Then follow the steps below to verify the setting or correct it for your
motor. DO NOT set it greater than 50/60 Hz unless the motor manufacturer
specifically approves operation at the higher frequency.
Action
(Starting point)
Press the
key once
Press the
key
Press the
/
Press the
key
setting (50 Hz/60 Hz), be sure to check the motor and machine specifications
with the respective manufacturer. Only operate the motor at elevated frequen-
cies after getting their approval. Otherwise, there is the danger of equipment
damage.
Set the AVR Voltage Setting – The inverter has an Automatic Voltage Regula-
tion (AVR) function. It adjusts the output voltage to match the motor's name-
plate voltage rating. The AVR smoothes out fluctuation in the input power
source, but note that it does not boost the voltage in the event of a brown-out.
Use the AVR setting (A082) that most closely matches the one for your motor.
• 200 V class: 200 / 215 / 220 / 230 / 240 VAC
• 400 V class: 380 / 400 / 415 / 440 / 460 / 480 VAC
Display
Speed command source setting
A001
Run command source setting
A002
01... Control terminals
01
02... Digital operator
03... ModBus network input
etc.
02... Digital operator (selected)
key to select
02
Stores parameter, returns to "A002"
A002
Display
Run command source setting
A002
Base frequency setting
A003
Default value for the base frequency
60.0
US = 60 Hz, Europe = 50 Hz
or
50.0
Set to your motor specs (your display
key to select
60.0
may be different)
Stores parameter, returns to "A003"
A003
Section 2-5
Func./Parameter
Func./Parameter