Parameter Warning Codes - Omron MX2 User Manual

200 v class three-phase input 0.1 to 15 kw 200 v class single-phase input 0.1 to 2.2 kw 400 v class three-phase input 0.4 to 15 kw
Hide thumbs Also See for MX2:
Table of Contents

Advertisement

Monitoring Trip Events, History, & Conditions
6-2-3

Parameter Warning Codes

242
Error Code
Rotat-
ing
Blinking Communication
Note Reset is not allowed in 10 second after trip.
Note When error E08, E14 and E30 occur, reset operation by RS terminal or STOP/
RESET key is not accepted. In this case, reset by cycling power. If still same
error occurs, perform initialization.
If set parameter is conflicted to other parameters, warning code is displayed
as follows.
Warning
code
001
Frequency upper limit (A061)
A
Frequency lower limit (A062)
A
002
005
Output Frequency setting (F001)
A
Multi-speed freq. 0 (A020)
Output Frequency setting (F001)
A
015
Multi-speed freq. 0 (A020)
025
Frequency lower limit (A062)
A
Start frequency (A082)
A
031
Start frequency (A082)
A
032
Start frequency (A082)
A
035
Start frequency (A082)
A
036
Start frequency (A082)
A
037
Output Frequency setting (F001)
A
085
Multi-speed freq. 0 (A020)
Multi-speed freq. 1-15
A
086
(A021-A035)
Name
Reset
RS input is ON or STOP/RESET key is
pressed.
Undervoltage
If input voltage is under the allowed level,
inverter shuts off output and wait with this indi-
cation.
Waiting to restart This indication is displayed after tripping before
restarting.
Restricted oper-
Commanded RUN direction is restricted in
b035.
ation command
Trip history
Trip history is being initialized.
initializing
No data
No trip/waning data exists.
(Trip monitor)
Communication between inverter and digital
error
operator fails.
Auto-tuning
Auto-tuning is completed properly.
completed
Auto-tuning error Auto-tuning fails.
Warning conditions
Section 6-2
Descriptions
> Max. Frequency (A004)
> Max. Frequency (A004)
> Max. Frequency (A004)
> Frequency upper limit (A061)
> Output Frequency setting (F001)
Multi-speed freq. 0 (A020)
> Frequency upper limit (A061)
> Frequency lower limit (A062)
> Output Frequency setting (F001)
Multi-speed freq. 0 (A020)
> Multi-speed freq. 1-15
(A021-A035)
> Jogging frequency (A038)
= Jump frequency
(A063/A063/A063±A064/
A066/A068)