List Of Registers; List Of Registers (Function Modes) - Omron MX2 User Manual

200 v class three-phase input 0.1 to 15 kw 200 v class single-phase input 0.1 to 2.2 kw 400 v class three-phase input 0.4 to 15 kw
Hide thumbs Also See for MX2:
Table of Contents

Advertisement

ModBus Data Listing
(iv) List of registers
Register
Function name
No.
1103h
Acceleration time (1)
1104h
1105h
Deceleration time (1)
1106h
1107h
Keypad Run key routing
1108h to
Unused
1200h
(v) List of registers (function modes)
Parameter group A
Register
Function name
No.
1201h
Frequency source
1202h
Run command source (*)
1203h
Base frequency
1204h
Maximum frequency
1205h
[AT] selection
1206h to
(Reserved)
120Ah
120Bh
[O] input active range start fre-
quency
120Ch
120Dh
[O] input active range end fre-
quency
120Eh
120Fh
[O] input active range start volt-
age
1210h
[O] input active range end volt-
age
1211h
[O] input start frequency select
1212h
Analog input filter.
1213h
EzSQ selection
1214h
(Reserved)
1215h
Multi speed operation selection
1216h
Multi-speed freq. 0
1217h
1218h
Multi-speed freq. 1
1219h
121Ah
Multi-speed freq. 2
121Bh
121Ch
Multi-speed freq. 3
121Dh
121Eh
Multi-speed freq. 4
121Fh
1220h
Multi-speed freq. 5
1221h
1222h
Multi-speed freq. 6
1223h
1224h
Multi-speed freq. 7
After changing the setting, keep the time 40 ms or longer before actually give run command
288
Function
R/W
Monitoring and setting items
code
F002 (high)
R/W
1 to 360000
F002 (low)
F003 (high)
R/W
1 to 360000
F003 (low)
F004
R/W
0 (forward rotation), 1 (reverse rotation) –
Inaccessible
Function
R/W
Monitoring and setting items
code
A001
R/W
0 (keypad potentiometer), 1 (control
circuit terminal block), 2 (digital opera-
tor), 3 (Modbus), 4 (option ), 6 (pulse
train input), 7 (easy sequence),
10 (operation function result)
A002
R/W
1 (control circuit terminal block), 2 (digi-
tal operator), 3 (Modbus), 4 (option)
A003
R/W
300 to "maximum frequency"
A004
R/W
300 to 4000 (10000)
A005
R/W
0 (switching between O and OI termi-
nals), 2 (switching between O terminal
and keypad potentiometer), 3 (switching
between OI terminal and keypad poten-
tiometer)
A011 (high)
R/W
0 to 40000(100000)
A011 (low)
A012 (high)
R/W
0 to 40000(100000)
A012 (low)
A013
R/W
0 to "[O]-[L] input active range end
voltage"
A014
R/W
"[O]-[L] input active range start voltage"
to 100
A015
R/W
0 (external start frequency), 1 (0 Hz)
A016
R/W
1 to 30 or 31 (500 ms filter ±0.1 Hz
with hysteresis)
A017
R/W
0 (disabling), 1 (PRG terminal) ,
2 (Always)
A019
R/W
0 (binary), 1 (bit)
A020 (high)
R/W
0 or "start frequency" to "maximum
frequency"
A020 (low)
R/W
A021 (high)
R/W
0 or "start frequency" to "maximum
frequency"
A021 (low)
R/W
A022 (high)
R/W
0 or "start frequency" to "maximum
frequency"
A022 (low)
R/W
A023 (high)
R/W
0 or "start frequency" to "maximum
frequency"
A023 (low)
R/W
A024 (high)
R/W
0 or "start frequency" to "maximum
frequency"
A024 (low)
R/W
A025 (high)
R/W
0 or "start frequency" to "maximum
frequency"
A025 (low)
R/W
A026 (high)
R/W
0 or "start frequency" to "maximum
frequency"
A026 (low)
R/W
A027 (high)
R/W
0 or "start frequency" to "maximum
frequency"
Section B-4
Data
resolution
0.01 [sec.]
0.01 [sec.]
Data
resolution
0.1 [Hz]
0.1 [Hz]
0.01 [Hz]
0.01 [Hz]
1 [%]
1 [%]
1
0.01 [Hz]
0.01 [Hz]
0.01 [Hz]
0.01 [Hz]
0.01 [Hz]
0.01 [Hz]
0.01 [Hz]
0.01 [Hz]

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents