Error Codes
Error code
Fins-
CX-
Gateway
Server
ERROR
ERROR
A hot start or cold start was
CODE:
CODE:
attempted immediately after the
(2605)
(2605)
Loop Controller performed a
direct recovery operation.
ERROR
ERROR
Power was turned OFF when
CODE:
CODE:
data was being transferred.
(2606)
(2606)
Probable cause
Probable cause
Possible remedy
Possible remedy
Cycle the power supply to the Loop Controller or restart
the Unit before sending the Operation Command.
Power was turned OFF when data was being transferred.
Turn ON the power supply and repeat the transfer
operation from the beginning.