Omron CX-PROCESS TOOL V5.2 - REV 10-2010 Operation Manual page 189

Table of Contents

Advertisement

User Link Tables
162
User Link Table Settings
Item
Number
Refresh period
Tag Name
Comment
Specify
p
y
Link Mode Constant, On change, External sync
Link
Li k
Memory
memory
Type
Memory
Address
A/D
Bit
Position
R/W
/
Range Conversion
Contact
Synchro-
Synchro-
nous Sig-
nization
nal
Read from ITEM/Write
to ITEM
Pulse Output
(See note 1.)
Output as CSV Tag
Information
Monitor Plus Tag
setting
Alarm Set
Note
1. EM1 to EM12 can be used in LCBVV Ver. 3.0 or later projects
2. Pulse outputs can be used in LCBVV Ver. 3.0 or later projects.
Setting
Entry number
For details on the entry number, refer to 3-5-4 Editing User
Link Tables.
The refresh cycle for CPU Unit data.
The cycle can be set to the system common operating
cycle, 0.01 s, 0.02 s, 0.05 s, 0.10 s, 0.20 s, 0.50 s, 1.00 s,
or 2.00 s
(If the user link table is pasted in a block diagram to make
software connections and the function block data is
downloaded to the Loop Control Board with the Update
User Link Table Refresh Cycle selection selected in the
CX-Process Tool, the setting made here will be ignored
and data refreshing with the CPU Unit will be performed
on the operating cycle of the function blocks that are the
destination of the software connections.)
16 characters max., any text string
23 characters max., any text string
Area in I/O memory of CPU Unit: CIO, W, H, DM, or EM0
(See note 2.)
The address of the word in I/O memory to be allocated
Analog or contact
00 to 15
RD (To Loop Controller)
Wr (From Loop Controller)
ON/OFF
0% value and 100% value
ITEM specified (function block address and ITEM number)
ON/OFF
Specify a read ITEM and/or WRITE item (function block
address and ITEM number)
Select to specify a one-shot pulse output when the signal
changes from OFF to ON. (Turns ON the output only once
during the refresh cycle for user link tables and writes to
the I/O memory of the CPU Unit.)
Enabled only when A/D is a contact and R/W is Wr (from
the Loop Control Board).
Select this option to add user link table tags to the SCADA
tag file or RS View tag file.
Note If this option is not selected when registering the user
link table, the user link table tags will not be output
even if adding user link table information is selected
during the output process.
Creates Monitor Plus tags. Select this option when
monitoring or setting the user link table from the
CX-Process Monitor Plus.
Creates alarm tags. If alarm tags are set, they can be
displayed in the CX-Process Monitor Plus Alarm Log
Screens.
Section
3-5