Omron CP - PROGRAMMING MANUAL 05-2007 Programming Manual page 295

Cp1h/cp1l cpu unit
Table of Contents

Advertisement

Data Movement Instructions
3-7-9
BLOCK SET: BSET(071)
Purpose
Ladder Symbol
Variations
Applicable Program Areas
Operands
Note
Operand Specifications
262
Copies the same word to a range of consecutive words.
BSET(071)
S
St
E
Variations
Executed Each Cycle for ON Condition
Executed Once for Upward Differentiation
Executed Once for Downward Differentiation Not supported
Immediate Refreshing Specification
Block program areas
OK
OK
S: Source Word
Specifies the source data or the word containing the source data.
St: Starting Word
Specifies the first word in the destination range.
E: End Word
Specifies the last word in the destination range.
St
to
E
Source data
Destination range
St
E
St and E must be in the same data area.
Area
CIO Area
Work Area
Holding Bit Area
Auxiliary Bit Area
Timer Area
Counter Area
S: Source word
St: Starting word
E: End word
Step program areas
Subroutines
OK
S
CIO 0 to CIO 6143
W0 to W511
H0 to H511
A0 to A959
A448 to A959
T0000 to T4095
C0000 to C4095
Section 3-7
BSET(071)
@BSET(071)
Not supported
Interrupt tasks
OK
St
E

Hide quick links: