Omron CP - PROGRAMMING MANUAL 05-2007 Programming Manual page 779

Cp1h/cp1l cpu unit
Table of Contents

Advertisement

High-speed Counter/Pulse Output Instructions
Ladder Symbol
Variations
Applicable Program Areas
Operands
Operand Specifications
746
Origin Search
Pulses are output using the specified method to actually drive the motor and
establish the origin based on origin proximity input and origin input signals.
Origin Return
The positioning system is returned to the pre-established origin.
ORG(889)
P
P: Port specifier
C
C: Control data
Variations
Executed Each Cycle for ON Condition
Executed Once for Upward Differentiation
Executed Once for Downward Differentiation Not supported
Immediate Refreshing Specification
Block program areas
OK
P: Port Specifier
The port specifier specifies the port where the pulses will be output.
P
0000 hex
Pulse output 0
0001 hex
Pulse output 1
0002 hex
Pulse output 2 (CP1H only)
0003 hex
Pulse output 3 (CP1H only)
0020 hex
Inverter positioning 0 (CP1L only)
0021 hex
Inverter positioning 1 (CP1L only)
C: Control Data
The value of C determines the origin search method.
15
12
11
8
7
C
Pulse output method (See note.)
0 hex: CW/CCW
1 hex: Pulse + direction
Mode
0 hex: Origin search
1 hex: Origin return
Note: Use the same pulse output method when using both pulse outputs 0 and 1.
Area
CIO Area
Work Area
Holding Bit Area
Auxiliary Bit Area
Timer Area
Step program areas
Subroutines
OK
OK
Port
4
3
0
Always 0 hex.
Always 0 hex.
P
---
---
---
---
---
Section 3-20
ORG(889)
@ORG(889)
Not supported
Interrupt tasks
OK
C
---
---
---
---
---

Hide quick links:

Advertisement

Table of Contents
loading