Connecting the EX9214 to Power

IN THIS SECTION

Connect Earth Ground to an EX Series Switch | 164

Connecting AC Power to an EX9214 Switch | 174
Powering On an AC-Powered EX9200 Switch | 177
Connecting DC Power to an EX9214 Switch | 179
Powering On a DC-Powered EX9200 Switch | 184
Connect Earth Ground to an EX Series Switch
IN THIS SECTION
Parts and Tools Required for Connecting an EX Series Switch to Earth Ground | 165
Special Instructions to Follow Before Connecting Earth Ground to an EX Series Switch | 171
Connecting Earth Ground to an EX Series Switch | 173
To ensure proper operation and to meet safety and electromagnetic interference (EMI) requirements,
you must connect an EX Series switch to earth ground before you connect power to the switch. You
must use the protective earthing terminal on the switch chassis to connect the switch to earth ground
(see
Figure 52 on page
174).
You must install the EX Series switch in a restricted–access location and ensure that the chassis is
always properly grounded. EX Series switches have a two–hole protective grounding terminal provided
on the chassis. See
Table 58 on page 165
switches. Under all circumstances, use this grounding connection to ground the chassis. For AC-
powered systems, you must also use the grounding wire in the AC power cord along with the two-hole
grounding lug connection. This tested system meets or exceeds all applicable EMC regulatory
requirements with the two-hole protective grounding terminal.
Ensure that a licensed electrician has attached an appropriate grounding lug to the grounding cable you
supply. Using a grounding cable with an incorrectly attached lug can damage the switch.
for the location of the earthing terminals on various EX Series
164