Lenovo Converged HX Series Installation And Service Manual page 219

Table of Contents

Advertisement

Check Lenovo Data Center Support site for an applicable retain tip or firmware update that applies to this
error.
Note: It may be necessary to disable unused option ROMs from BIOS setup.
• Diagnostic Code:
136F07E6
Full Sensor Name (Sensor Name In SDR):
PCIE_Status
Sensor Type:
Critical Interrupt
Event Severity:
Critical
Description:
Bus Correctable Error - Asserted
Message:
A single bit error is occurred in PCIe bus. This error will be repaired automatically.
Actions:
If this node and/or any attached cables were recently installed, moved, serviced or upgraded,
1. Reset adapter and any attached cables.
2. Reload Device Driver.
3. If the device is not recognized, re-configuring the slot to Gen1 or Gen2 may be required.
Gen1/Gen2 settings can be configured via F1 Setup -> System Settings -> Devices and I/O Ports
-> PCIe Gen1/Gen2/Gen3 Speed Selection.
• Diagnostic Code:
136F08E6
Full Sensor Name (Sensor Name In SDR):
PCIE_Status
Sensor Type:
Critical Interrupt
Event Severity:
Critical
Description:
Bus Uncorrectable Error - Asserted
Message:
A multiple bits error is occurred in PCIe bus. This error will cause system to be hang up.
Actions:
1. Check Lenovo Data Center Support site for an applicable retain tip or firmware update that applies to
this error.
2. If this node and/or any attached cables were recently installed, moved, serviced or upgraded,
a. Reset adapter and any attached cables.
b. Reload Device Driver.
c. If the device is not recognized, re-configuring the slot to Gen1 or Gen2 may be required.
Appendix A. TMM error messages
205