Check Lenovo Data Center Support site for an applicable retain tip or firmware update that applies to this
error.
Note: It may be necessary to disable unused option ROMs from BIOS setup.
• Diagnostic Code:
136F07E6
Full Sensor Name (Sensor Name In SDR):
PCIE_Status
Sensor Type:
Critical Interrupt
Event Severity:
Critical
Description:
Bus Correctable Error - Asserted
Message:
A single bit error is occurred in PCIe bus. This error will be repaired automatically.
Actions:
If this node and/or any attached cables were recently installed, moved, serviced or upgraded,
1. Reset adapter and any attached cables.
2. Reload Device Driver.
3. If the device is not recognized, re-configuring the slot to Gen1 or Gen2 may be required.
Gen1/Gen2 settings can be configured via F1 Setup -> System Settings -> Devices and I/O Ports
-> PCIe Gen1/Gen2/Gen3 Speed Selection.
• Diagnostic Code:
136F08E6
Full Sensor Name (Sensor Name In SDR):
PCIE_Status
Sensor Type:
Critical Interrupt
Event Severity:
Critical
Description:
Bus Uncorrectable Error - Asserted
Message:
A multiple bits error is occurred in PCIe bus. This error will cause system to be hang up.
Actions:
1. Check Lenovo Data Center Support site for an applicable retain tip or firmware update that applies to
this error.
2. If this node and/or any attached cables were recently installed, moved, serviced or upgraded,
a. Reset adapter and any attached cables.
b. Reload Device Driver.
c. If the device is not recognized, re-configuring the slot to Gen1 or Gen2 may be required.
Appendix A. TMM error messages
205