Commissioning
4.6 Extended Safety
● You can adapt the STO function according to your requirements in the following screen.
● Set the following in the above screen:
● Close the screen form.
● Also, close any other STO screens.
● If you do not use any other safety function, go directly to Section Activate settings
4.6.3.7

Setting SS1

The appearance of the SS1 screen form depends on which mode you set when selecting the
safety functions.
152
① ②
F-DI input filter (debounce time) and monitoring for simultaneous operation
(discrepancy):
The method of functioning of the two filters is described in section F-DI signal filtering
(Page 77).
Forced dormant error detection of the switch-off signal paths:
You define the monitoring of the forced dormant error detection in another screen form
(Setting forced dormant error detection and the PROFIsafe address (Page 148)). Set
this time to the maximum value (9000 hours).
No setting required
(Page 158).
Safety Integrated Function Manual, SINAMICS G120 and G120C
Function Manual, 01/2011, FW 4.4, A5E03052391B AB