4.9.5.4
Safely Limited Speed, SLS
Table 4- 11
"Safely Limited Speed" (SLS) function
No.
1.
Initial state
The inverter is in the "Ready" state (p0010 = 0).
•
The inverter signals neither faults nor alarms of the safety functions (r0945, r2122, r2132).
•
SLS is not active.
•
2.
Switch on the motor (ON command).
Note: Select a higher motor speed than the SLS limit currently set (providing the machine allows
this).
3.
Ensure that the correct motor is running.
4.
Select the SLS monitoring speed to be checked.
Notes: If you are using several SLS monitoring speeds, repeat the test for each of the monitoring
speeds.
Test each configured activation, e.g. via digital inputs and PROFIsafe.
5.
Select SLS while the motor is running.
6.
Check the following:
The motor speed decreases according to the selected ramp time. The motor then rotates below
•
the parameterized safely limited speed.
The inverter signals:
•
"SLS is selected" (r9720.4 = 0).
"SLS is active" (r9722.4 = 1).
7.
Deselect SLS.
8.
Check the following:
The motor speed increases until the setpoint is reached.
•
The inverter signals neither faults nor alarms of the safety functions.
•
The inverter signals:
•
"SLS is deselected" (r9720.4 = 1).
"SLS is not active" (r9722.4 = 0).