4.5.1.2

Setting STO

● You can adapt the STO function according to your requirements in the following screen.
● Set the following in the above screen:
● Close the screen.
4.5.1.3

Activate settings

● Click "Copy parameters" and then click "Activate settings":
● You are prompted to allocate a password if the password = 0 (factory setting).
● Confirm the prompt for saving your settings (copy RAM to ROM).
● Switch off the inverter supply voltage.
● Wait until all LEDs on the inverter go dark. Now switch on the inverter supply voltage
Safety Integrated Function Manual, SINAMICS G120 and G120C
Function Manual, 01/2011, FW 4.4, A5E03052391B AB
– ① ② F-DI input filter (debounce time) and monitoring for simultaneous operation
(discrepancy):
The method of functioning of the two filters is described in the section entitled F-DI
signal filtering (Page 77).
– ③ ④ Time interval for forced dormant error detection:
Information regarding forced dormant error detection can be found in the Forced
dormant error detection (test stop) (Page 72) section.
If you try to set a password that is not permissible, the old password will not be changed.
Further information can be found in the section Password (Page 71).
again. Your settings only become effective after this power-on reset.
Commissioning
4.5 Basic Safety
111