Commissioning
4.6 Extended Safety
4.6.3.2

Setting forced dormant error detection and the PROFIsafe address

● Select the values compatible with your application.
– Further information can be found in the section Forced dormant error detection (test
● If you only want to use STO, close this screen and go to the section Enabling safety
● In all other cases, go to the next section.
4.6.3.3

Setting the gear ratio and tolerance

148
– ① This signal triggers a forced dormant error detection and resets the timer.
Interconnect this signal with a binector of your choice, for example a digital input or a
control bit in the field bus.
– ② You must conduct a forced dormant error detection for this signal. Interconnect this
binector with a signal of your choice, for example a digital input or a status bit in the
field bus.
– ③ Time interval for forced dormant error detection.
stop) (Page 72).
PROFIsafe address
Enter the same PROFIsafe address as a hexadecimal value, that you defined in the
hardware configuration (F_Dest_Add).
See sectionConfiguring communication in STEP 7 (telegram 30) (Page 100).
functions (Page 151).
Safety Integrated Function Manual, SINAMICS G120 and G120C
Function Manual, 01/2011, FW 4.4, A5E03052391B AB