Description
2.5 Safely Limited Speed, SLS
2.5.3.2

Switching between monitoring thresholds

When SLS is active, you can switch between four different levels.
Note
Switching between the SLS levels is only possible via PROFIsafe.
PROFIsafe control word 1
Bit 10
0
0
1
1
Behavior of SLS when switching over the monitoring
If you switch from a higher to a lower SLSlevel, then the inverter only monitors the speed
with the lower SLS level after the delay time has expired.
If you switch from a lower to a higher SLS level, then the inverter immediately monitors the
speed with the higher SLS level.
36
Selected SLS level
Bit 9
0
Level 1
1
Level 2
0
Level 3
1
Level 4
Safety Integrated Function Manual, SINAMICS G120 and G120C
p9531[0]
p9531[1]
p9531[2]
p9531[3]
Function Manual, 01/2011, FW 4.4, A5E03052391B AB