Siemens SINAMICS G120 Function Manual page 103

Hide thumbs Also See for SINAMICS G120:
Table of Contents

Advertisement

● Double-click the PROFIsafe telegram to open the properties dialog and set the input and
● Then choose the "PROFIsafe" tab page:
● Save and compile your project and download the data to your SIMATIC CPU.
● Close HW Config.
Safety Integrated Function Manual, SINAMICS G120 and G120C
Function Manual, 01/2011, FW 4.4, A5E03052391B AB
output range to address 14, for example:
F_Dest_Add:
Set a unique PROFIsafe address for the inverter.
F_WD_Time:
Set a value which is larger than the cycle time of your safety program. If your safety
program is called every 150 ms, for example, in OB35, set the value of F_WD_Time to
200.
Interfaces
3.3 Activation via PROFIsafe
101

Advertisement

Table of Contents
loading

This manual is also suitable for:

Sinamics g120c

Table of Contents