● Set the following in this screen form:
4.6.1.12

Activate settings

● Click "Copy parameters" and then click "Activate settings":
● You are prompted to allocate a password if the password = 0 (factory setting).
● Confirm the prompt for saving your settings (copy RAM to ROM).
● Switch off the inverter supply voltage.
● Wait until all LEDs on the inverter go dark. Now switch on the inverter supply voltage
Safety Integrated Function Manual, SINAMICS G120 and G120C
Function Manual, 01/2011, FW 4.4, A5E03052391B AB
Enable the function
Delay time between selecting SDI and the active SDI:
The delay time must be greater than the time that the motor requires, when SDI is
selected, for braking with the maximum load from the maximum speed down to
standstill.
Tolerance for the permissible motion in the monitored direction (Unit: degree)
Reaction when the monitoring responds
See also section: STOP reactions (Page 192)
Behavior when the motor is switched off
Also see section: Switching off the motor when SDI is active (Page 44)
⑥ ⑦
If you interconnect the monitoring with speed limits p1051 and p1052, the
inverter limits the speed when SDI is active.
If you try to set a password that is not permissible, the old password will not be changed.
Further information can be found in the section Password (Page 71).
again. Your settings only become effective after this power-on reset.
Commissioning
4.6 Extended Safety
131