Components in separate control cabinets
If the components are located in separate control cabinets, the wiring between the SM326
I/O module and the F-DIs on the inverter must be installed such that it is protected against
cross and short-circuits.
Transfer the two signals for activating a safety function via wires in separate lines. In the
example, the signals for terminal 5 and 7 are transferred via the first line. The signals for
terminal 6 and 8 are then transferred via the second line.
Figure 3-16
Safety Integrated Function Manual, SINAMICS G120 and G120C
Function Manual, 01/2011, FW 4.4, A5E03052391B AB
Interconnecting the inverter and SM326 I/O module in separate control cabinets
Interfaces
3.2 Activation via F-DI
91