Commissioning
4.9 Acceptance test - Completion of commissioning
4.9.5.3

Safe Stop 1, SS1

Table 4- 10
"Safe Stop 1" function (SS1)
No.
1.
Initial state:
The inverter is in the "Ready" state (p0010 = 0).
The inverter signals neither faults nor alarms of the safety functions (r0945, r2122, r2132).
SS1 is not active.
2.
Switch on the motor (ON command).
3.
Ensure that the correct motor is running.
4.
Select SS1 while the motor is running.
Note: Test each configured activation, e.g. via digital inputs and PROFIsafe.
5.
Check the following:
The motor speed decreases in line with the selected ramp time (if necessary, use a stopwatch).
The inverter signals:
"SS1 is selected" (r9720.1 = 0).
"SS1 is active" (r9722.1 = 1).
The motor coasts to a standstill after the standstill detection threshold has been reached.
The inverter signals:
"STO is active" (r9772.0 = 1).
A mechanical brake brakes the motor and holds it to ensure that it remains at a standstill.
The inverter signals neither faults nor alarms of the safety functions.
6.
Deselect SS1.
7.
Check the following:
The inverter signals neither faults nor alarms of the safety functions.
The inverter signals:
"STO is not active" (r9722.0 = 0).
"SS1 is deselected" (r9720.1 = 1).
8.
Switch the motor off (OFF1 command) and then on again (ON command).
9.
Ensure that the correct motor is running.
172
Description
Safety Integrated Function Manual, SINAMICS G120 and G120C
Function Manual, 01/2011, FW 4.4, A5E03052391B AB