Commissioning
4.9 Acceptance test - Completion of commissioning
4.9.6

Completion of certificate

Document your machine's data for each drive based on the following specifications.
Parameters of the safety functions
The function test does not detect all faults in the parameter assignment of safety functions,
e.g. forced dormant error detection time or filtering time of fail-safe inputs. Therefore, check
all parameters once more.
Designation of the 1st drive
Designation of the 2nd drive
...
Checksums of the safety functions
The inverter calculates checksums across all parameters and safety functions. The
parameters of Basic Safety and Extended Safety have their own checksums.
When you change the safety function settings, the inverter calculates new checksums. This
means that subsequent changes in your machine can be tracked.
In addition to the individual checksums of the parameters, the inverter calculates and saves
the following values:
1. The "total" checksum across all checksums.
2. Time of the last parameter changed.
Processor 1
Designation of the
p9798
1st drive
p9799
...
...
176
Basic Safety
Processor 2
Processor 1
p9898
p9398[0]
p9899
p9399[0]
All parameter values checked
Checksums
Extended Safety
Processor 2
[0] = Parameter
[1] = Actual
values
p9728[0]
p9728[1]
p9729[0]
p9729[1]
Safety Integrated Function Manual, SINAMICS G120 and G120C
Function Manual, 01/2011, FW 4.4, A5E03052391B AB
Total
Time stamp
r9781[0]
r9782[0]