Transducer Block Enumerations - Emerson Rosemount OCX8800A Manual

Oxygen and combustibles transmitter
Table of Contents

Advertisement

Manual
00809-0500-4880
8.7 

Transducer block enumerations

8.7.1 
Calibration states
During a running calibration procedure, the states below reflect the current step
that the calibration is running in.
Refer to
Table 8-4: Calibration State: Values
Index
0
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
Rosemount OCX8800A
Table
8-4.
CAL_STATE description
Idle
Apply O
low gas
2
Flow O
low gas
2
Read O
low gas
2
Apply O
high gas
2
Flow O
high gas
2
Read O
high gas
2
Apply combustibles low gas
Flow combustibles low gas
Read combistibles low gas
Apply combustibles high gas
Flow combustibles high gas
Read combustibles high gas
Stop gas
Purge
Abort
F
OUNDATION
December 2022
Operator acknowledgement
required to continue?
Yes, calibration can also be
initiated from internally generated
events.
Yes, if parameter Solenoids
Present is 0.
No
No
Yes, if parameter Solenoids
Present is 0.
No
No
Yes, if parameter Solenoids
Present is 0.
No
No
Yes, if parameter Solenoids
Present is 0..
No
No
Yes, if parameter Solenoids
Present is 0.
No
Yes, if parameter Solenoids
Present is 0.
Fieldbus
139