Node Address; Foundation Fieldbus Function Blocks; Resource Block; Transducer Block - Emerson Rosemount 5600 Series Reference Manual

Radar level transmitter with foundation fieldbus protocol
Hide thumbs Also See for Rosemount 5600 Series:
Table of Contents

Advertisement

Rosemount 5600 Series

Node Address

F
OUNDATION
fieldbus
function blocks
MECHANICAL
INSTALLATION
ELECTRICAL
INSTALLATION

Power Supply

3-2
The transmitter is shipped at a temporary address to allow a host to
automatically assign an address.

Resource Block

The Resource block contains diagnostic, hardware, electronics, and mode
handling information. There are no linkable inputs or outputs to the Resource
Block. For more information on the Resource Block, refer to Appendix D:
Resource Block.

Transducer Block

The Transducer block allows a user to view the different parameters, errors,
and diagnostics in the transmitter. It also includes information to configure the
transmitter for the application it is used in. For more information on the
Transducer block, refer to Appendix B: Level Transducer Block.

Analog Input (AI) Block

The Analog Input (AI) Function Block processes the measurements from
sensors and makes them available to other function blocks. The output value
from the AI block is in engineering units and contains a status indicating the
quality of the measurement. The AI block is widely used for scaling
functionality. For more information on the Analog Input Block, refer to
Appendix E: Analog-Input Block.
For all Rosemount 5600 Radar Level Transmitter mechanical installations
refer to the Rosemount 5600 Radar Level Manual (00809-0100-4024).
"Mounting the Rod Antenna" on page 2-12
"Mounting the Cone Antenna - PTFE sealing" on page 2-16
"Mounting the Process Seal Antenna" on page 2-19
"Mounting the Cone Antenna in a Still-pipe/Bridle" on page 2-22
"Mounting an Extended Cone Antenna" on page 2-26
"Mounting a Cone Antenna with Flushing Connections" on page 2-29
The transmitter requires separate power within the range 24-240 V AC or DC
0-60Hz. Tighten the terminal screws to ensure adequate contact.
Fieldbus Voltage limits: 9 to 32 V
Current Draw: 21 mA
For I.S. Applications:
U
< 30 V
i
I
< 300 mA
i
P
< 1.3 W
i
µ
C
= 0
F
i
L
= 0 mH
i
Reference Manual
00809-0100-4025, Rev AA
May 2003