Calibration
6.1 

Overview

During calibration, the operator applies two calibration gases with known O
concentrations and one calibration gas with a known COe concentration to the
transmitter. Slope and constant values are calculated to determine if the
transmitter is correctly measuring net concentration of O
the industrial process.
Before calibrating the transmitter, verify that the calibration gas parameters are
correct by setting the test gas values to use when calibrating it. Refer to
Configuration and
There are three calibration methods available to the transmitter: automatic,
operator-initiated, and manual. You can access calibration commands and menus
with the Field Communicator or the optional local operator interface (LOI).
6.2 

Fully automatic calibration

If the transmitter is equipped with calibration solenoids, you can program it to
automatically calibrate without any operator action.
Refer to
autocalibration using HART
calibration.
6.2.1 
Set up autocalibration using the local operator
interface (LOI)
If necessary, refer to
with calibration solenoids to use automatic calibration.
Procedure
1. From the operating display, press Right to select SYSTEM from the first
2. From the SYSTEM first column submenu, press Right to select the Calib
3. From the Calib Setup second column submenu, press Right to select the
4. Scroll down to the last item, Use Solenoids. If the transmitter is equipped
5. Press Up to select O2 Out Tracks. Select Yes or No to determine if the
Rosemount OCX8800A
start-up.
Set up autocalibration using the local operator interface (LOI)
®
Figure 4-4
column submenu.
Setup second column submenu.
third column parameter list.
with calibration solenoids and you want timed automatic calibration, select
Yes.
transmitter will update the O
to set up the transmitter for fully automatic
for reference. The transmitter must be equipped
lock value.
2
Calibration
December 2022
2
and combustibles in
2
or
Set up
93