00809-0500-4880
The nine arithmetic functions are: flow compensation linear, flow compensation
square root, flow compensation approximate, BTU flow, traditional multiply and
divide, average, summer, fourth order polynomial, and simple HTG compensate
level.
This arithmetic function block supports mode control (Auto, Manual, or Out of
Service). There is no standard alarm detection in this block.
Table 8-28: Arithmetic (ARTHM) Block
Index number
Parameter
4
ALERT_KEY
29
ARITH_TYPE
30
BAL_TIME
31
BIAS
21
BIAS_IN_1
23
BIAS_IN_2
25
BIAS_IN_3
36
BLOCK_ALM
6
BLOCK_ERR
27
COMP_HI_LIM
Rosemount OCX8800A
Units
Description
None
The identification number of the plant
unit. This information may be used in the
host for sorting alarms, etc.
None
The set of 9 arithmetic functions applied
as compensation to or augmentation of
the range extended input.
Seconds
Specifies the time for a block value to
match an input, output, or calculated
value or the time for dissipation of the
internal balancing bias.
None
The bias value.
None
The bias value for IN_1.
None
The bias value for IN_2.
None
The bias value for IN_3.
None
This block alarm is used for all
configuration, hardware, connection
failure, or system problems in the block.
The cause of the alert is entered in the
subcode field. The first alert to become
active will set the Active status in the
Status parameter. As soon as the
Unreported status is cleared by the alert
reporting task, another block alert may be
reported without clearing the Active
status, if the subcode has changed.
None
The summary of active error conditions
associated with the block. The possible
block errors are
error
override
variable has Bad status
failure
service
reports none or a subset of these error
conditions.
EU of PV
Determines the high limit of the
compensation input.
F
OUNDATION
December 2022
Block configuration
,
,
Simulate active
Local
,
Input failure/process
,
,
Readback failed
, and
. Each function block
Other
Fieldbus
,
Output
Out of
195