Potential cause
The downstream block is sending back a Quality of Bad or a Status of Not Invited.
Recommended action
See the appropriate downstream block diagnostics for corrective action.
Mode will not change to AUTO
Potential cause
Target mode not set.
Recommended action
Set target mode to something other than OOS.
Potential cause
The link is not configured; the status shows Not connected.
Recommended action
Configure the IN link to the block.
Potential cause
The upstream block is sending back a Quality of Bad or a Status of Not Invited.
Recommended action
See the appropriate upstream block diagnostics for corrective action.
Mode will not change to CAS
Potential cause
Target mode not set.
Recommended action
Set target mode to something other than OOS.
Potential cause
The link for Cascade input (CAS_IN) is not configured.
Recommended action
Configure the CAS_IN link to the block.
Potential cause
The upstream block is sending back a Quality of Bad or a Status of Not Invited.
Recommended action
See the appropriate upstream block diagnostics for corrective action.