Table 8-29: BLOCK_ERR Conditions
Condition
number
4
5
6
7
8
9
10
11
12
13
14
15
8.10.2 
Modes
The ARTHM block supports the following modes:
Manual (Man): The block output (OUT) may be set manually.
Automatic (Auto): OUT reflects the analog input measurement or the simulated
value when simulation is enabled.
Out of Service (O/S): The block is not processed. FIELD_VAL and PV are not
updated, and the OUT status is set to Bad: Out of Service. The BLOCK_ERR
parameter shows Out of Service. In this mode, you can make changes to all
configurable parameters.
The target mode of a block may be restricted to one or more of the supported
modes.
8.10.3 
Alarm detection
A block alarm is generated whenever the BLOCK_ERR has an error bit set.
Block errors
grouped into five levels of priority:
Priority
number
0
Rosemount OCX8800A
Condition name and description
Local Override: The actual mode is LO.
Device Fault State Set
Device Needs Maintenance Soon
Input Failure/Process Variable has Bad Status: The parameter linking to
IN is indicating a Bad status.
Output Failure
Memory Failure
Lost Static Data
Lost NV Data
Readback Check Failed
Device Needs Maintenance Now
Power Up
Out of Service: The actual mode is out of service.
defines the types of block errors for the arithmetic block. Alarms are
Priority description
The priority of an alarm condition changes to
caused the alarm is corrected.
(continued)
F
Fieldbus
OUNDATION
December 2022
after the condition that