Emerson Rosemount OCX8800A Manual page 129

Oxygen and combustibles transmitter
Table of Contents

Advertisement

Manual
00809-0500-4880
2. In the Transmitter Options menu, select either Simulate Switch or PWA
3. Select Enable to enable PWA simulation or Disable to disable the simulation
4. Once the method is complete, select Resource → Simulate PWA in the
5. Now select Simulation On or Simulation Off from the PWA Simulate
6. To simulate PlantWeb Alerts, select the alerts listed under Failed Active,
7. To simulate block alarms, select the alarms listed under Detailed Status in
8. Select Resource → PWA SubStatus to see the active PWA alarms and masks.
9. Select Resource → Status → Detailed Statusor Transducer → Status → 
8.5.1 
Support resource block errors
Resource block
Out of Service: Set whenever the resource block actual mode is out of service.
Power Up: Set whenever the FF card powers up.
Block Configuration Error: Configure Error is used to indicate that you had
selected an item in FEATURES_SEL or CYCLE_SEL that was not in FEATURES or
CYCLE_TYPE respectively.
Simulation active: Set whenever the Fieldbus simulate switch is set to On at the
Fieldbus card or software simulate option enabled.
Transducer block
Out of Service: Set whenever the transducer block actual mode is out of
service.
Input Failure: Set whenever there is a communication error between the
Fieldbus card and the transmitter.
Simulation Active: Set whenever the Fieldbus Simulate switch is set to On at
the Fieldbus card or the Software simulate option is enabled.
Other error: Set whenever XD_ERROR is non-zero.
Rosemount OCX8800A
Simulate.
feature.
resource block.
If the simulation is enabled, the PWA Simulate parameter is configurable.
Otherwise it is read-only.
parameter.
When PWA simulation is on, all of the PWA active parameters and the
resource and transducer block status parameters are configurable.
Otherwise they are read-only.
Maintenance Active, and Advisory Active (Resource → Simulate PWA).
the resource block (Resource → Simulate PWA) or under Detailed Status in
the transducer block (Transducer → Simulate Status).
Select Fail Active, Maintenance Active, or Advisory Active for active PWA
alarms.
Detailed Status to see the resource or transducer block detailed status.
F
Fieldbus
OUNDATION
December 2022
129