Figure 8-10: Situation #2 Diagram
A. Empty tank
B. Measured at the transmitter
Table 8-23
Table 8-23: Analog Input Function Diagram for a Pressure Transmitter Used
in Level Measurement (Situation #2)
Parameter
L_TYPE
XD_SCALE
OUT_SCALE
8.8.16 
Differential pressure transmitter to measure flow
Situation
The liquid flow in a line is to be measured using the differential pressure across
an orifice plate in the line, and the flow measurement will be used in a flow
Rosemount OCX8800A
lists the appropriate configuration settings.
F
OUNDATION
Configured values
Indirect
2 to 9 psi (0.1 to 0.6 BarG)
0 to 16 ft (0 to 4.9 m)
Fieldbus
December 2022
163