Test Conditions Summary; Appliance Operation And Test Settings; Settings & Run Notes - FPI I2450M Manual

Wood-fired fireplace insert
Table of Contents

Advertisement

Test Conditions Summary

Testing conditions for all runs fell within allowable specifications of ASTM E3053 and
ASTM E2515. A summary of facility conditions, fuel burned, and run times is listed below.
Ambient (°F)
Runs
Pre
Post
1
77
81
2
83
79
4
82
80
This is the weight of the kindling and startup fuel
1
Total test time was 190 min, high fire test load burn duration was 163 min.
2

Appliance Operation and Test Settings

The appliance was operated according to procedures as described in the Operations
Manual, found in Appendix B submitted with this report. Detailed run information can be
found in Appendix A submitted with this report.
The air setting used for the low fire test was the lowest possible setting available on the
appliance.
Settings & Run Notes
Pre-Burn Air Setting
Run 1
N/A – Cold Start Ignition
Air control set to High Fire Setting in
Run 2
accordance with ASTM E3053
Air control set to High Fire Setting in
Run 4
accordance with ASTM E3053
Page | 9
Average
Relative
Barometric
Humidity (%)
Pressure
(In. Hg.)
Pre
Post
31.9
27.5
29.86
26.5
27.8
30.13
25
31.8
29.96
Air control set to high fire test setting, blower off for first 20 min, then
set to high.
Air control set to low fire test setting, blower off for first 30 min, then
set to low.
Air control set to medium fire test setting, blower off for first 20 min,
then set to low.
Project # 19-469
Preburn
Test Fuel
Test Fuel
Fuel
Weight
Moisture
Weight
(lbs)
(lbs)
7.1
1
22.6
21.5
25.8
21.8
26.4
Test Run Air and Fan Settings
Model: I2450M
Test Run
Time
(%DB)
(Min)
22.4
190
2
21.5
525
22.3
471