RST
Function
Returns
\
Function
Returns
FRST
Function
Returns
1. Factory Reset does not affect advanced parallel configuration acknowledgment (does not affect
power supply configuration (Single, Master or Slave roles does not change).
2. Execution time for this command is ~250mS.
3. FRST command sets USB communication interface.
4.10.6

Output Commands

PV <NR2>
Function
Parameters
Query
Returns
MV?
Query
Returns
PC <NR2>
Function
Parameters
Query
Returns
MC?
Query
Returns
Reset setting. Refer to Table 2-6.
<DSC> OK
Repeat last command. If \<CR> is received, the power supply will repeat the last
command
<DSC> OK
Restore factory reset parameters. Refer to Table 2-6 & Table 2-7
None
Set digital programming output voltage value in Volts
Range is limited by the power supply model, OVP and UVP settings. Refer to
Table 4-4
PV?
<NR2> 5-digits format
Returns a measured output voltage
<NR2> 5 digits format
Set digital programming output current value in Amperes
Range is limited by the power supply model. Refer to Table 4-5.
PC?
<NR2> 5-digits format
Returns a measured output current
<NR2> 5 digits format