4.2.7

Setting Unit in Remote, Local Lockout or Local Mode

If power supply is in Local mode, it can receive communication commands & queries. If a
command is received, power supply will execute and change its mode to Remote. If a query is
received, power supply will reply and remain in the Local mode.
Remote Mode:
If a communication command is received, power supply will perform the command and change its
mode to Remote.
If power supply is in Remote mode, the REM indicator illuminates.
Parameters cannot be changed via the front panel. If an attempt is made to change parameters via
the front panel, Current display shows REM message for 2 seconds.
It is possible to return to Local mode by pressing the front panel SYST button, followed by Current
encoder press or via communication command SYSTem:REMote[:STATe] LOC.
Local Lockout Mode:
If power supply is in Local Lockout mode, REM indicator illuminates.
Parameters cannot be changed via the front panel. If an attempt is made to change parameters via
the front panel, Current display shows LLO message for 2 seconds.
It is possible to return to the Remote mode by the communication command
SYSTem:REMote[:STATe] REM or by AC power recycle.