Maintenance; Replaceable Parts; Part Replacement Guidelines - YASKAWA GA800 Maintenance & Troubleshooting

Ac drive for industrial applications, three-phase 200/400 v class: 1 to 150/600 hp, 6-phase/12-pulse 400 v class: 75 to 600 hp
Hide thumbs Also See for GA800:
Table of Contents

Advertisement

1.3

Maintenance

The drive Maintenance Monitors keep track of component wear and tell the user when the end of the estimated
performance life is approaching. The Maintenance Monitors prevent the need to shut down the full system for
unexpected problems. Users can set alarm notifications for the maintenance periods for these drive components:
• Cooling fan
• Electrolytic Capacitor
• Soft charge bypass relay
• IGBT
Contact Yaskawa or your nearest sales representative for more information about part replacement.

Replaceable Parts

DANGER! Electrical Shock Hazard. Do not examine, connect, or disconnect wiring on an energized drive. Before servicing,
disconnect all power to the equipment and wait for the time specified on the warning label at a minimum. The internal capacitor
stays charged after the drive is de-energized. The charge indicator LED extinguishes when the DC bus voltage decreases below 50
Vdc. When all indicators are OFF, remove the covers before measuring for dangerous voltages to make sure that the drive is safe. If
you do work on the drive when it is energized, it will cause serious injury or death from electrical shock.
You can replace these parts of the drive:
• Control circuit terminal board
• Cooling fan, circulation fan
• Keypad
Note:
Make sure that you use a keypad that has a flash number of 1004 or later. Keypads that have a flash number of 1003 or earlier will not show
characters correctly.
If there is a failure in the main circuit, replace the drive.
If the drive is in the warranty period, contact Yaskawa or your nearest sales representative before you replace parts.
Yaskawa reserves the right to replace or repair the drive as specified by the Yaskawa warranty policy.

Part Replacement Guidelines

Table 1.7
shows the standard replacement period for replacement parts. When you replace these parts, make sure that
you use Yaskawa replacement parts for the applicable model and design revision number of your drive.
Cooling fan
*1
Electrolytic capacitor
*1
If there is damage to parts that you cannot repair or replace, replace the drive.
Note:
These conditions are provided for the purpose of replacing parts to maintain performance. Unsatisfactory conditions or heavy use will make
it necessary for you to replace some parts more frequently than other parts. Performance life estimate is based on the yearly average of these
use conditions.
• Ambient Temperature Setting
–IP20/UL Open Type: 40 °C (104 °F)
–IP00/UL Open Type: 40 °C (104 °F)
–IP20/UL Type 1: 30 °C (86 °F)
–IP55/UL Type 12 Heatsink External Mounting; front side: 40 °C (104 °F)
–IP55/UL Type 12 Heatsink External Mounting; back side: 30 °C (86 °F)
• Load factor
80%
• Operating rate
24 hours a day
YASKAWA TOEPYAIGA8001B GA800 Drive Maintenance & Troubleshooting
Table 1.7 Standard Replacement Period
Parts

1.3 Maintenance

Standard Replacement Period
10 years
10 years
1
25