Advertisement

3.11

L: Protection Functions

L1: Motor Protection

No.
Name
(Hex.)
L1-01
Motor Overload (oL1)
Protection
(0480)
L1-02
Motor Overload Protection
Time
(0481)
L1-03
Motor Thermistor oH Alarm
Select
(0482)
L1-04
Motor Thermistor oH Fault
Select
(0483)
L1-05
Motor Thermistor Filter
Time
(0484)
L1-08
oL1 Current Level
(1103)
L1-09
oL1 Current Level for Motor
2
(1104)
L1-13
Motor Overload Memory
Selection
(046D)
YASKAWA TOEPYAIGA8001B GA800 Drive Maintenance & Troubleshooting
V/f
CL-V/f
OLV
CLV
AOLV
Sets the motor overload protection with electronic thermal protectors.
0 : Disable
1 : Variable Torque
2 : Constant Torque 10:1 Speed Range
3 : Constant Torque 100:1 SpeedRange
4 : PM Variable Torque
5 : PM Constant Torque
6 : Variable Torque (50Hz)
Note:
When only one motor is connected to a drive, set L1-01 = 1 to 6 [Enabled]. External thermal
relays are not necessary in these conditions.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the operation time for the electronic thermal protector of the drive to prevent damage to the
motor. Usually it is not necessary to change this setting.
V/f
CL-V/f
OLV
CLV
AOLV
Sets drive operation when the PTC input signal entered into the drive is at the oH3 [Motor Overheat
Alarm] detection level.
0 : Ramp to Stop
1 : Coast to Stop
2 : Fast Stop (Use C1-09)
3 : Alarm Only
V/f
CL-V/f
OLV
CLV
AOLV
Sets the drive operation when the PTC input signal to the drive is at the oH4 [Motor Overheat Fault
(PTC Input)] detection level.
0 : Ramp to Stop
1 : Coast to Stop
2 : Fast Stop (Use C1-09)
V/f
CL-V/f
OLV
CLV
AOLV
Sets the primary delay time constant for the PTC input signal entered to the drive. This parameter
prevents accidental motor overheat faults.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the reference current for the motor 1 thermal overload detection. When the current level > 0.0 A,
you cannot set this value < 10% of drive rated current.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the reference current for the motor 2 thermal overload detection. When the current level > 0.0 A,
you cannot set this value < 10% of drive rated current.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the function that keeps the current electronic thermal protector value when the drive stops
receiving power.
0 : Disabled
1 : Enabled

3.11 L: Protection Functions

Description
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Default
(Range)
Determined by A1-02
(0 - 6)
1.0 min
(0.1 - 5.0 min)
3
(0 - 3)
1
(0 - 2)
0.20 s
(0.00 - 10.00 s)
0.0 A
(0.0 A or 10% to 150% of
the drive rated current)
0.0 A
(0.0 A or 10 to150% of the
drive rated current)
1
(0, 1)
3
225