3.12 n: Special Adjustment

n6: Online Tuning

No.
Name
(Hex.)
n6-01
Online Tuning Selection
(0570)
n6-05
Online Tuning Gain
(05C7)
Expert
n6-11
Online Resistance Tuning
(1B56)
Expert

n7: EZ Drive

No.
Name
(Hex.)
n7-01
Damping Gain for Low
Frequency
(3111)
Expert
n7-05
Response Gain for Load
Changes
(3115)
Expert
n7-07
Speed Calculation Gain1
(3117)
Expert
n7-08
Speed Calculation Gain2
(3118)
Expert
n7-10
Pull-in Current Switching
Speed
(311A)
Expert
n7-11
Drv Mode Switch Hysteresis
Band
(311B)
Expert
n7-13
Driving Method Switching
Time
(311D)
Expert
n7-17
Resistance
TemperatureCorrection
(3122)
238
V/f
CL-V/f
OLV
CLV
AOLV
Sets the type of motor data that Online Tuning uses for OLV control.
0 : Disabled
1 : Line-to-Line Resistance Tuning
2 : Voltage Correction Tuning
V/f
CL-V/f
OLV
CLV
AOLV
Sets the compensation gain when n6-01 = 2 [Online Tuning Selection = Voltage Correction Tuning].
Usually it is not necessary to change this parameter.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the responsiveness for online resistor tuning. Set this parameter to approximately 1.000 to enable
the function. The function is disabled when the value is 0.000.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the oscillation suppression gain for the low speed range.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the response gain related to changes in the load.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the speed calculation gain during usual operation. Usually it is not necessary to change this
setting.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the speed calculation gain during a speed search.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the speed range to operate with the pull-in current command. Drive rated frequency = 100%
value. If there is a large quantity of oscillation when you operate in the low speed range, increase the
setting value.
V/f
CL-V/f
OLV
CLV
AOLV
Usually it is not necessary to change this setting. Sets the hysteresis level for Switching Speed set in
n7-10 [Pull-in Current Switching Speed].
When the speed is lower than n7-10 + n7-11 during acceleration, the drive enables pull-in current.
Note:
• When the drive accelerates, it enables these settings:
–Motor speed ≤ n7-10 + n7-11: n8-51 [Pull-in Current @ Acceleration]
–Motor speed > n7-10 + n7-11: b8-01 [Energy Saving Control Selection]
• If there is a large quantity of oscillation when you operate in the low speed range, increase the
setting value.
• When it is most important to save energy in the low speed range, decrease the setting value.
V/f
CL-V/f
OLV
CLV
AOLV
Sets a time to enable the pull-in current commands.
If there is a large quantity of oscillation at speeds around n7-10 [Pull-in Current Switching Speed],
decrease the setting in 20 ms decrements.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the function to adjust for changes in the motor resistance value caused by changes in the
temperature.
0 : Invalid
1 : Valid (Only 1 time)
2 : Valid (Every time)
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
YASKAWA TOEPYAIGA8001B GA800 Drive Maintenance & Troubleshooting
Default
(Range)
0
(0 - 2)
1.0
(0.1 - 50.0)
0.000
(0.000 - 1.000)
Default
(Range)
1.0
(0.1 - 10.0)
100
(10 - 1000)
15.0
(1.0 - 50.0)
25.0
(1.0 - 50.0)
10.0%
(0.0 - 100.0%)
5.0%
(1.0 - 20.0%)
100 ms
(0 - 1000 ms)
1
(0 to 2)