3.13 o: Keypad-Related Settings
No.
Name
(Hex.)
o2-05
Home Mode Freq Ref Entry
Mode
(0509)
o2-06
Keypad Disconnect
Detection
(050A)
o2-07
Keypad RUN Direction @
Power-up
(0527)
o2-09
Reserved
(050D)
o2-23
External 24V Powerloss
Detection
(11F8)
RUN
o2-24
LED Light Function
Selection
(11FE)
o2-26
Alarm Display at Ext. 24V
Power
(1563)
o2-27
bCE Detection Selection
(1565)

o3: Copy Keypad Function

No.
Name
(Hex.)
o3-01
Copy Keypad Function
Selection
(0515)
o3-02
Copy Allowed Selection
(0516)
246
V/f
CL-V/f
OLV
CLV
AOLV
Sets the function that makes it necessary to push
reference value while in Drive Mode.
0 : ENTER Key Required
1 : Immediate / MOP-style
V/f
CL-V/f
OLV
CLV
AOLV
Sets the function that stops the drive if you disconnect the keypad connection cable from the drive or
if you damage the cable while the keypad is the Run command source.
0 : Disabled
1 : Enabled
V/f
CL-V/f
OLV
CLV
AOLV
Sets the direction of motor rotation when the drive is energized and the keypad is the Run command
source.
0 : Forward
1 : Reverse
-
V/f
CL-V/f
OLV
CLV
AOLV
Sets the function to give a warning if the backup external 24 V power supply turns off when the main
circuit power supply is in operation.
0 : Disabled
1 : Enabled
V/f
CL-V/f
OLV
CLV
AOLV
Sets the function to show the LED status rings and keypad LED lamps.
Note:
When you initialize the drive with parameter A1-03 [Initialize Parameters], the drive will not
reset this parameter.
0 : Enable Status Ring & Keypad LED
1 : LED Status Ring Disable
2 : Keypad LED Light Disable
V/f
CL-V/f
OLV
CLV
AOLV
When you connect a backup external 24 V power supply, this parameter sets the function to trigger
an alarm when the main circuit power supply voltage decreases.
Note:
The drive will not run when it is operating from one 24-V external power supply.
0 : Disabled
1 : Enabled
V/f
CL-V/f
OLV
CLV
AOLV
Sets drive operation if the Bluetooth device is disconnected when you operate the drive in Bluetooth
Mode.
0 : Ramp to Stop
1 : Coast to Stop
2 : Fast Stop (Use C1-09)
3 : Alarm Only
4 : No Alarm Display
V/f
CL-V/f
OLV
CLV
AOLV
Sets the function that saves and copies drive parameters to a different drive with the keypad.
0 : Copy Select
1 : Backup (drive → keypad)
2 : Restore (keypad → drive)
3 : Verify (check for mismatch)
4 : Erase (backup data of keypad)
V/f
CL-V/f
OLV
CLV
AOLV
Sets the copy function when o3-01 = 1 [Copy Keypad Function Selection = Backup (drive →
keypad)].
0 : Disabled
1 : Enabled
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
to use the keypad to change the frequency
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
YASKAWA TOEPYAIGA8001B GA800 Drive Maintenance & Troubleshooting
Default
(Range)
0
(0, 1)
1
(0, 1)
0
(0, 1)
-
0
(0, 1)
2
(0 - 2)
1
(0, 1)
3
(0 - 4)
Default
(Range)
0
(0 - 4)
0
(0, 1)