There Is Audible Noise From The Drive Or Motor Cables When You Energize The Drive; The Ground Fault Circuit Interrupter (Gfci) Trips During Run; Motor Rotation Causes Unexpected Audible Noise From Connected Machinery - YASKAWA GA800 Maintenance & Troubleshooting

Ac drive for industrial applications, three-phase 200/400 v class: 1 to 150/600 hp, 6-phase/12-pulse 400 v class: 75 to 600 hp
Hide thumbs Also See for GA800:
Table of Contents

Advertisement

2.10 Troubleshooting Without Fault Display
Causes
The motor torque is not sufficient.
The drive and motor system reached the torque limit.
The load is more than the internal torque limit as specified by the drive rated
current.
There Is Audible Noise from the Drive or Motor Cables when You Energize the
Drive
Causes
The relay switching in the drive is making too much noise.

The Ground Fault Circuit Interrupter (GFCI) Trips During Run

Causes
There is too much leakage current from the drive.

Motor Rotation Causes Unexpected Audible Noise from Connected Machinery

Causes
The carrier frequency and the resonant frequency of the connected machinery
are the same.
The drive output frequency and the resonant frequency of the connected
machinery are the same.
144
Use a larger motor.
Note:
If these items are correct, the demand on the motor is more than the motor capacity:
• Parameter settings are correct.
• The drive does not detect ov [Overvoltage].
• Examine the values set in L7-01 to L7-04 [Torque Limit] and increase them if necessary.
Note:
If the torque limit is enabled, deceleration time can increase because the drive cannot output
more torque than the limit.
• If H3-02, H3-10, H3-06 = 10, 11, 12, 15 [MFAI Function Select = Torque Limit] has been set,
examine the settings for the MFAIs.
• Examine the values set in H3-02, H3-10, and H3-06.
• Use U1-13 to U1-15 [Terminal A1, A2, A3 Input Voltage] to make sure that the analog input
values set to terminals A1, A2, and A3 are applicable.
Replace the drive with a larger capacity model.
• Use C6-02 [Carrier Frequency Selection] to decrease the carrier frequency.
• Connect a noise filter to the input side of the drive power supply.
• Connect a noise filter to the output side of the drive.
• Isolate the control circuit wiring from the main circuit wiring.
• Use a metal cable gland to wire the drive.
• Shield the periphery of the drive with metal.
• Make sure that the drive and motor are grounded correctly.
• Make sure that ground faults have not occurred in the wiring or motor.
• Increase the GFCI sensitivity or use GFCI with a higher threshold.
• Use C6-02 [Carrier Frequency Selection] to decrease the carrier frequency.
• Decrease the length of the cable used between the drive and the motor.
• Install a noise filter or AC reactor on the output side of the drive. Set C6-02 = 1 [2.0 kHz] when
connecting an AC reactor.
• Disable the internal EMC filter.
• Adjust C6-02 to C6-05 [Carrier Frequency].
• Set C6-02 = 1 to 6 [Carrier Frequency Selection = Frequency other than Swing PWM].
Note:
If C6-02 = 7 to A [Carrier Frequency Selection = Swing PWM], the drive will not know if the
noise comes from the drive or the machine.
• Adjust d3-01 to d3-04 [Jump Frequency].
• Put the motor on a rubber pad to decrease vibration.
YASKAWA TOEPYAIGA8001B GA800 Drive Maintenance & Troubleshooting
Possible Solutions
Possible Solutions
Possible Solutions
Possible Solutions

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents