N5: Feed Forward Control - YASKAWA GA800 Maintenance & Troubleshooting

Ac drive for industrial applications, three-phase 200/400 v class: 1 to 150/600 hp, 6-phase/12-pulse 400 v class: 75 to 600 hp
Hide thumbs Also See for GA800:
Table of Contents

Advertisement

No.
Name
(Hex.)
n4-66
Flux Estimate Response
@Low Freq
(1B86)
n4-67
Estimate Gain Switchover
Freq
(1B87)
n4-68
Speed Estimation Filter
Time
(1B88)
n4-69
Flux Control Response
(1B89)
n4-70
Speed Command Comp @
Low Freq
(1B8A)
n4-71
Flux Estimation Method
(1B8B)
Expert
n4-72
Speed Feedback Mode
(1B8C)
n4-73
PGo Recovery Selection
(1B8D)
n4-74
Limit of Flux Loop
(1B8E)

n5: Feed Forward Control

No.
Name
(Hex.)
n5-01
Feed Forward Control
Selection
(05B0)
n5-02
Motor Inertia Acceleration
Time
(05B1)
n5-03
Feed Forward Control Gain
(05B2)
n5-04
Speed Response Frequency
(05B3)
RUN
Expert
YASKAWA TOEPYAIGA8001B GA800 Drive Maintenance & Troubleshooting
V/f
CL-V/f
OLV
CLV
AOLV
Sets the responsiveness of the magnetic flux estimation in low speed ranges, where 0 ≤ the output
frequency, which is < n4-67 [Estimate Gain Switchover Freq]. Usually it is not necessary to change
this setting.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the switching frequency for estimation gain for these parameters:
n4-63 [Speed EstimateResponse@High Freq]
n4-64 [Speed Estimate Response@Low Freq]
n4-65 [Flux Estimate Response@High Freq]
n4-66 [Flux Estimate Response @Low Freq]
Usually it is not necessary to change this setting.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the primary delay time constant for the speed estimation value. Usually it is not necessary to
change this setting.
V/f
CL-V/f
OLV
CLV
AOLV
Unifies control of magnetic flux to make motor vibrations more stable.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the function to make the drive more stable when operating at low speeds. Usually it is not
necessary to change this setting.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the flux estimation method. Usually it is not necessary to change this setting.
0 : Method 1
1 : Method 2
V/f
CL-V/f
OLV
CLV
AOLV
Sets the requirement for an encoder option when A1-02 = 4 [Control Method Selection = Advanced
Open Loop Vector].
0 : Without Encoder
1 : With Encoder
V/f
CL-V/f
OLV
CLV
AOLV
Sets the restart mode to Without Encoder Mode or the With Encoder Mode when an encoder is
disconnected.
0 : Without Encoder
1 : With Encoder
V/f
CL-V/f
OLV
CLV
AOLV
Sets the control level for flux loop control output.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the feed forward function.
0 : Disabled
1 : Enabled
V/f
CL-V/f
OLV
CLV
AOLV
Sets the length of time for the motor to accelerate from the stopped to the maximum frequency with a
single motor at the rated torque. Inertia Tuning automatically sets the motor acceleration time.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the ratio between load inertia and motor inertia. Inertia Tuning automatically sets the
Feedforward Control Gain value.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the response frequency for the speed reference. Usually it is not necessary to change this
parameter.
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
3.12 n: Special Adjustment
Default
(Range)
1.50
(0.50 - 3.00)
6.00 Hz
(0.00 - E1-04 setting)
0.001 s
(0.001 - 0.010 s)
1.00
(0.00 - 60.00)
1.00 Hz
(0.00 - 6.00 Hz)
0
(0, 1)
0
(0, 1)
0
(0, 1)
250%
(100 - 500%)
Default
(Range)
0
(0, 1)
Determined by C6-01, E5-
01, and o2-04
(0.001 - 10.000 s)
1.00
(0.00 - 100.00)
Determined by A1-02
(0.00 - 500.00 Hz)
3
237

Hide quick links:

Advertisement

Table of Contents
loading